About this task
Map (link) CIMPLICITY points to Modbus data addresses by creating register-mapping Register Mapping Records definitions within the configuration file.
todo:
To maximize throughput:
Procedure
-
Map:
- Boolean points to coil (0X) or input status (1X) data addresses.
- Analog points to input register (3X) or holding register (4X) data addresses.
Avoid gaps in allocated data addresses.
-
Edit the configuration file to specify the
- Communications port parameters,
- Trace log parameters, and
- Modbus register limits.