Timer Block

Purpose

The Timer (TM) block functions as a time counter by incrementing or decrementing its value.

Features

The Timer block:

  • Is a secondary block.
  • Passes the value (0 or 1) from its upstream block to the downstream block.
  • Can be chained from a Digital Input block, a Digital Alarm block, or a Boolean block. The Timer block can also be chained from a Digital Output block but only if the Digital Output block is part of an chain that starts with a scanned block.
  • Cannot be chained from an AR or DR block, as these blocks are not processed by SAC.
  • Starts counting from a preset value or zero.
  • Increments its value up to 365 days or until reset.
  • Decrements its value to a target value or to zero.
  • Triggers an alarm upon reaching a target value.
  • Can suspend counting using a digital block.
  • Resets when the digital upstream block changes from zero to one.

 

Typical Uses

Example

Fields

Important Notice