Statistical Data Block

Purpose

The Statistical Data (SD) block collects and performs statistical calculations on data.

Features

The Statistical Data block:

  • Is a statistical block.
  • Can be used as a stand-alone block.
  • Can only be followed by a Statistical Control block, if appropriate.
  • Receives data from Analog Input, Analog Output, Analog Alarm, and Calculation blocks through the Input field, not from a previous block's Next Block field.
  • Supports from 12 to 50 groups and from 1 to 25 observations per group.
  • Performs alarming and charting on control and warning limits.
  • Provides out of process control alarms.
  • Operates in Automatic mode by accepting automatic updates.
  • Operates in Manual mode by accepting manual updates from operators or from Easy Database Access programs.
  • Can be used in a chain with exception-based processing if you do not enter a time in the Wait Time field.

 

See Also