DGCM Field RTU - Legacy
Manufacturing for this product has been discontinued. As an alternative, please refer to the iBox.
DGCM Field RTU - Legacy
Manufacturing for this product has been discontinued. As an alternative, please refer to the iBox.
Fault/Level Detections
Effective fault isolation is a key feature for grid reliability. The Multilin DGCM provides early warning for downstream overcurrent and earth faults. It can be programmed to isolate a faulted segment, either independently or from the remote. The Multilin DGCM also offers control, monitoring and diagnostics in one integrated, efficient design.
Overcurrent Protection
Instantaneous and time overcurrent functions are available for phase, neutral and negative sequence currents. A variety of time curves are provided, including IEEE/ANSI, IEC A/B/C/long time inverse/short time inverse, definite time and user-programmable curves.
Cold Load Pickup
The Multilin DGCM can be programmed to block instantaneous overcurrent elements, and raise the pickup time of overcurrent elements, when a cold load condition is detected. The cold load condition is detected during the closing of the breaker on a feeder that has been de-energized for a long time. The feeder inrush and motor accelerating currents during breaker closing may be above some overcurrent protection settings.
Overvoltage (OV) Detection
The phase OV protection guards voltage sensitive feeder loads and circuits against sustained OV conditions. It generates alarms when the voltage exceeds the selected voltage level for the specified time delay.
Undervoltage (UV) Detection
The phase UV detection alerts utilities against sustained UV conditions. The UV detector generates an alarm when the voltage drops below the selected voltage level after a specified time delay.
Power Loss
The Multilin DGCM can detect a power loss condition in each phase of the power distribution line. Open/close commands are blocked, unless currents and voltages of each phase fall below minimum set values.
Application Overview
Metering & Monitoring
The Multilin DGCM provides high accuracy metering and recording of all AC signals, measuring the following key parameters:
Basic Measurements
- Current: Ia, Ib, Ic, In
- Phase-to-phase and phase-to-ground voltages for bus and line: Van, Vbn, Vcn, Vbb, Vab, Vbc, Vca
- Active power (per-phase and total): Wa, Wb, Wc, W
- Reactive power (per-phase and total): VARa, VARb, VARc, VAR
- Total active, reactive and apparent energy: MWh, MVARh, MVAh
- Power factor (per-phase and total)
- Frequency
Power Quality Measurements
- Voltage sag/swell
- Current unbalance
- Demand: voltage, current, active power, apparent power, energy, temperature
- 2nd to 15th harmonic for current
- 2nd to 15th harmonic for voltage
- THD in 20% for current
- THD in 20% for voltage
Data Management & Diagnostic
Event Recorder
To enable more effective distribution, post fault analysis and troubleshooting, the Multilin DGCM provides an integrated event recorder and detailed diagnostic features. The event recorder offers:
• Storage for up to 1024 consecutive events
Trending and Data Logging
The Multilin DGCM provides a 200 channel RMS recorder for advanced disturbance diagnostic features.
The Multilin DGCM data logger helps in better understanding the analog channel behavior, by sampling at a selectable time interval rate of 1 to 60 minutes.
The Multilin DGCM event recorder enables users to analyze the sequence of events . Each event is stored with the event number, date, time and analog data of interest.
Communications
The Multilin DGCM utilizes industry standard communications technologies, making it one of easiest and flexible controllers to use and integrate into new and existing SCADA or DMS infrastructures.
Multiple Protocol Support
Multiple communication ports and protocols allow for remote control and easy access to device and system information. All communication ports are capable of simultaneous communications.
Simultaneous industry standard protocols supported:
- DNP 3.0 – Serial and Ethernet
- Modbus Serial and Ethernet
- IEC 60870-5-104
Integrated Cellular
The Multilin DGCM’s integrated cellular modem eliminates the need for external wireless devices, which reduces infrastructure costs.
Several options for MDS™ radios when purchased with enclosure:
- MDS iNET-II
- MDS TransNet
Software
Software and Configuration
The EnerVista Suite is an industry-leading set of software programs that simplifies every aspect of using the Multilin DGCM. EnerVista provides the tools to monitor the status of the protected asset, maintain the controller and integrate information measured by the Multilin DGCM into SCADA or DMS monitoring systems.
EnerVista Launchpad
EnerVista Launchpad is a powerful software package that provides users with of the setup and support tools needed for configuring and maintaining GE Vernova’s Multilin products. The setup software within Launchpad allows the configuration of devices in real-time, by communicating via serial, Ethernet or modem connections, or offline, by creating device setting files to be sent to devices at a later time.
Recommended Products & services
Capacitor Bank Controller - Legacy
Manufacturing for this product has been discontinued. Please contact us if you have any inquiries.
Capacitor Bank Controller - Legacy
Manufacturing for this product has been discontinued. Please contact us if you have any inquiries.
Key Features
- Auto/Manual or Local/Remote control
- Automatic control based on Time, Temperature, Voltage and VAR
- Control override based on Temperature and voltage
- Over/Under Voltage settings
- Perpetual calendar with time zones and day light savings Options for multiple seasons
- Close operations counters
Volt/VAR control
Voltage regulator controllers and Capacitor bank controllers can operate as part of an integrated Volt/VAR Control (IVVC) scheme or as a Centralized Volt/VAR control (CVVC) system. The IVVC or CVVC system works to achieve two key objectives:
Optimize Voltage - through ‘Conservation of Voltage’ that leads to reduced demand, that may result in decreased generation up to 6%.
Increased efficiency- through improved power factor and reduced VAR which helps to reduce power line losses.
Capacitor Bank Control
Robust Design
As a complete package, the Multilin Capacitor Bank Controller is offered in a NEMA-4 certified cabinet that is suitable for operation of harsh environments with an operating range of -40°C to + 60°C (-40°F to +140°F).
Mode of Operation
To provide optimal application flexibility, the Multilin Capacitor Bank Controller offers two modes or methods of operation in which the device can be implemented to control the Capacitor Bank:a) Manual Mode (Local Control or Remote Control). b) Automatic Mode
Manual Mode – Local Control
In this mode, it is possible to Open or Close the Capacitor Bank, locally, from the large pushbuttons located on the front panel of the Multilin Capacitor Bank Controller. For increased operational reliability and operator safety, inhibit functions configured in the unit will continue to operate as defined.
Manual Mode – Remote Control
In this mode, the commands for Open or Close of the Capacitor Bank are received via communication channels from the SCADA or an integrated Volt/VAR system. This communication channel can be provided via optional radio or cellular communications.
Automatic Mode
In automatic mode, the Multilin Capacitor Bank Controller issues commands to Open or Close the Capacitor Bank. In this mode, the Capacitor Bank is controlled
Key Capacitor Bank Control Features:
- Four Season Configuration
- Time Schedule Control
- Temperature control
- Voltage control
- VAR Control (Min Delta KVAR)
- Inhibit Controls
Key Features
- Star Neutral Overcurrent (Blown Fuse Indication)
- Customized automation schemes using FlexLogic™
- Expandable inputs and outputs for advanced applications
Protection
Reverse Power Detection
The Multilin Capacitor Bank Controller includes a Reverse Power Detection function, which defines the minimum pickup required to detect reverse power conditions.
Neutral Overcurrent Protection (Blown Fuse Condition)
In situations where the capacitor bank has been tripped due to a neutral current unbalance situation, the Multilin Capacitor Bank Controller will execute a reclose action to validate the state of the fault, ensuring the fault was not transient in nature. This automatic reclose action ensures maximizes system reliability.
Automation
The Multilin Capacitor Bank Controller offers powerful I/O and programmable FlexLogic™ options for advanced automation control, reducing the need for additional programmable controllers or discrete control relays. The Multilin Capacitor Bank Controller has three identical set point groups. The activation of the group can be done either from the HMI or via a Digital Input.
Set point group control
The Multilin Capacitor Bank Controller has three identical set point groups. The activation of the group can be done either from the HMI or via a Digital Input.
Virtual Inputs and Outputs
The Multilin Capacitor Bank Controller provides 32 virtual inputs and 32 virtual outputs that provide users the ability to send commands to the device. The Multilin Capacitor Bank Controller can accept commands from SCADA, through the front HMI, or front USB port to issue commands such as Open or Close.
Command Setting
The Multilin Capacitor Bank Controller has the ability to force commands from the menu structure accessible through the Multilin EnerVista setup software that runs on a PC.
FlexLogic™
Advanced FlexLogic in the Multilin Capacitor Bank Controller provides the ability to create customized control schemes. This minimizes the need for auxiliary components and wiring, thus reducing complexity and costs.
Key Features
- Metering - current, voltage, power, frequency, PF, Harmonics
- Event Recorder - Up to 256 time tagged events
- Temperature via RTD inputs
- Enhanced system diagnostics & reporting
Metering & monitoring
The Multilin Capacitor Bank Controller provides high accuracy metering and recording of AC signals, measuring the following key parameters:
- Phase-Ground Voltage (kV)
- Phase-to-Phase Voltage (kV)
- Line Voltage (kV)
- A, B, and C Phase Currents (A)
- Line Current (A)
- Ground Current (A)
- 3-Phase Active Power (kW)
- 3-Phase Reactive Power (kVAR)
- 3-Phase Apparent Power
- Delta Reactive Power (KVAR)
- Power Factor (Lag or Lead)
- 2nd to 8th harmonic up to 20% – for current
- 2nd to 8th harmonic up to 20% – for voltage
- THD in 20% – for current
- THD in 20% – for voltage
- Temperature [ ºC ]
These data points can be easily integrated into a customer’s database for seamless viewing through a SCADA or DMS system.
The Multilin Capacitor Bank Controller has the ability to monitor the following setpoints / conditions and issue an alarm if measured values fall outside of specified limits:
- Minimum voltage limit
- Bank switch failed
- Switching alarm (Reverse Power)
- Total close counter reached
- Max Daily operation counter reached
- Minimum VAR Delta (variation)
- Minimum Volt. Delta (variation)
- Neutral overcurrent
Event recorder
To significantly reduce time and enable more effective disturbance, post fault analysis and troubleshooting, the Multilin Capacitor Bank Controller provides an integrated event recorder and detailed diagnostic features.
Data Management and Diagnostics
The Multilin Capacitor Bank Controller provides advanced disturbance diagnostic features that significantly reduce the time and costs associated with troubleshooting power system events and reconstruction. Recording functions include enhanced diagnostics with a 10 channel RMS recorder Data Logger.
Statistics & Counters
The Multilin Capacitor Bank Controller provides counters which records key operational parameters to aid in enabling preventative maintenance programs. The Multilin Capacitor Bank Controller includes many counters & statistical values.
Advanced Device Health Diagnostics
Comprehensive device health diagnostic tests are performed by the Multilin Capacitor Bank Controller during startup and continuously at runtime to test its own major functions and critical hardware. These diagnostic tests monitor for conditions that could impact the Multilin Capacitor Bank Controller’s performance, evaluates the potential impact and criticality of this condition and presents the device status to operators, via SCADA and/or through the front panel display.
Communications
The Multilin Capacitor Bank Controller utilizes industry standard, communications technologies making it one of easiest and most flexible controllers to use and integrate into new and existing SCADA or DMS infrastructures. Supported communication protocols include:
- DNP 3.0
- Modbus RTU (RS485)
Multiple communication ports and protocols allow for remote control and easy access to device and system information. All communication ports are capable of simultaneous communications. The Multilin Capacitor Bank Controller can also communicate to Volt/VAR or SCADA systems via wireless communications media. The supported wireless media includes:
- Wireless Radio (MDS or customer specific)
- GSM/GPRS
- Pre-wired for future radio
Front Panel
Front Panel Quick Keys
Front Penel quick keys provides direct access to key individual setting parameters
Key Features
4-Level device security to maintain authorized access only
Simplified device configuration software tool and industry leading suite of software tools to manage and maintain Multilin devices.
Security
The Multilin Capacitor Bank Controller and associated software tools provide a suite of security features that ensure only approved personnel can make changes to the configuration of the system or execute commands. These functions enable a utility to meet NERC/CIP requirements.
Password Security
The Multilin Capacitor Bank Controller offers multiple levels of password security to limit access control based on settings or command levels. There are four levels of password security provided:
- Local Settings Access
- Local Control Access
- Remote Settings Access
- Remote Control Access
Local Access refers to users making changes using the front USB serial port and the HMI. Remote Access refers to users making changes using the rear RS485 port.
EnerVista™ Software
The EnerVista™ Suite is an industry-leading set of software programs that simplifies every aspect of using the Multilin Capacitor Bank Controller The EnerVista™ suite provides all the tools to monitor the status of the protected asset, maintain the controller, and integrate information measured by the DGCC into SCADA or the DMS monitoring systems. The ability to easily view sequence of events is an integral part of the setup software, as postmortem event analysis is critical to proper system operation.
Learn More
Recommended Products & services
DFP200 Digital Feeder Protection - Legacy
Manufacturing for this product has been discontinued. For more information, contact us.
The DFP200 is a digital relay system that provides distribution feeder protection, control, metering, and monitoring. It uses waveform sampling of the current and voltage inputs at 32 times per cycle. Incorporating multiple functions in one package eliminates the need for expensive discrete components.
DFP200 Digital Feeder Protection - Legacy
Manufacturing for this product has been discontinued. For more information, contact us.
The DFP200 is a digital relay system that provides distribution feeder protection, control, metering, and monitoring. It uses waveform sampling of the current and voltage inputs at 32 times per cycle. Incorporating multiple functions in one package eliminates the need for expensive discrete components.
Recommended Products & services
DFP100 Digital Feeder Relay - Legacy
Manufacturing for this product has been discontinued. For more information, contact us.
DFP100 Digital Feeder Relay - Legacy
Manufacturing for this product has been discontinued. For more information, contact us.
Recommended Products & services
DFF Digital Frequency Relay - Legacy
Manufacturing for this product has been discontinued. As an alternative, please refer to the F60,
DFF Digital Frequency Relay - Legacy
Manufacturing for this product has been discontinued. As an alternative, please refer to the F60,
Recommended Products & services
DDS Digital Distribution System - Legacy
Manufacturing for DDS has been discontinued. Please see individual product pages for more information.
The DDS family of devices provide economical protection, control, metering and monitoring functionality to electrical utilities and industrial customers.
DDS Digital Distribution System - Legacy
Manufacturing for DDS has been discontinued. Please see individual product pages for more information.
The DDS family of devices provide economical protection, control, metering and monitoring functionality to electrical utilities and industrial customers.
DDFR - Legacy
Distributed Digital Fault Recorder
Manufacturing for this product has been discontinued.
DDFR - Legacy
Distributed Digital Fault Recorder
Manufacturing for this product has been discontinued.
Data Recording
Key Features
- Retrieves and Archives Transient Fault Records, Sequence of Event Records, and Disturbance Records recorded in protection relays distributed across the substation
- Automatically merges Events recorded in protection relays distributed across the network into a single substation wide Sequence of Event Record
- Stores months of fault and disturbance records internally, facilitating local substation analysis
- Discrete second Ethernet port will allow isolation between the network LAN and the IED’s connected to the DDFR.
Data Recording
The DDFR will detect that new information has been recorded in a relay and automatically retrieve and archive this data. Information that will be archived from protection relays include:
- Transient Fault Records
- Sequence of Event Records
- Disturbance Records
The DDFR is a Transient Fault, Sequence of Event, and Disturbance record archiving system that will seamlessly make available all of the recorded power system information necessary for performing post mortem fault and disturbance analysis.
Sequence of Event Record (SOE)
The DDFR will retrieve the Event Records stored in protection relays distributed across a substation and merge all of these Events into a Station-Wide Sequence of Event Record. Connecting the protection relays to an IRIG-B time clock will synchronize the relay internal clocks with 1 millisecond accuracy and enable the DDFR to create a Station-Wide Event Record that will be an exact representation of the sequence of operations that occurred in the substation.
Sequence Of Event Records (SOE)
Transient Fault Records
Transient Fault Records (also known as Oscillography records) that are recorded in protection relays will be retrieve by the DDFR and stored in its internal memory space. All Transient Fault Records will be archived using a naming convention that will make it easy for users to relate the Transient Fault records with a particular substation fault. Each record will be stored with a name that includes the exact date and time that the record was initially triggered. If the Transient Fault record was originally recorded in the relay as a COMTRADE file, the DDFR will store this record in its native format; if the protection relay stores it’s record in another format, such as a CSV file, the DDFR will automatically convert this file into the COMTRADE-1999 format so that the record can be analyzed using a standard COMTRADE viewer.
Disturbance Records
Protections relays that are capable of recording Disturbance Records that are used for analyzing extended or evolving power system disturbances such as Voltage Sags or Swells will be retrieved and archived be the DDRF. All Disturbance Records will be archived using a naming convention that will make it easy for users to relate the Disturbance records with a particular power system disturbance. Each record will be stored with a name that includes the exact date and time that the record was initially triggered. Disturbance records will be stored in COMTRADE format and if needed, first convert this file to a COMTRADE file from its native format.
Key Features
- Effortlessly archives recorded data to a permanent enterprise network location or server for remote investigation and analysis
- Non-volatile, solid state storage able to store months worth of fault and disturbance information locally inside the DDFR.
Entreprise Network Archiving
The DDFR Archiving System will automatically copy all data stored in DDFR’s located throughout a companies wide area network into a centralized network location allowing users to analyze fault and disturbance data without having to be at the same location as the DDFR. This DDFR Archiving System that runs on coma network PC or Server can retrieve data from multiple DDFR’s thereby creating a permanent enterprise wide library of all past disturbances on your power system. The information collected by the DDFR Archiving System will be categorized in separate directories for each DDFR, making it easy for users to identify data about faults and disturbances related to each individual substation.
Archive data collected in DDFR’s distributed across the network into a centralized, accessible network location
Viewing Archived Records
Users can analyze sequence of Event Records, Transient Fault Records, and Disturbance Records that have been stored on a DDFR or archived onto a network location by the DDFR Archiving System by using the EnerVista DDFR Setup Software. The DDFR Setup Software’s Event Record viewer and COMTRADE viewer can access archived records to provide local or remote analysis capability to anyone with access to network storage location.
Sequence of Event Viewer
The EnerVista™ DDFR Setup Software contains a Sequence of Event viewer that allows for easy analysis of the Events stored in the DDFR or archived to the network location. Each recorded event will contain detailed information including:
- Timestamp of Event
- Description of the Event
- Name of Substation
- Name of Source Relay
- Model of the Source Relay
The Sequence of Event viewer provides the ability to sort the recorded events by any of the available fields of information or to perform queries to show only the events that are necessary for troubleshooting a particular fault.
COMTRADE Viewer
The COMTRADE viewer that is included with the EnerVista DDFR Setup Software provides the ability of analyzing the Transient Fault Records and Disturbance Records that have been archived by the DDFR. This full featured COMTRADE viewer allows for analyzing records in a standard time based format that shows the magnitude of all measured quantities, or in Phasor diagram view that shows the magnitude and angle differences between any of the parameters. The COMTRADE viewer can also perform a harmonic analysis on all measured Phasor quantities and display the harmonic content for every point in the record up to the 25th harmonic.
Meet Standards DDFR Requirements
When used with advanced microprocessor based relays such as the UR family, the DDFR System meets or exceeds requirements of International Standards for Digital Fault Recording.
Recommended Products & services
DBF Digital Breaker Failure - Legacy
Manufacturing for this product has been discontinued. As an alternative, please refer to the 8 Series and UR Family relays
DBF Digital Breaker Failure - Legacy
Manufacturing for this product has been discontinued. As an alternative, please refer to the 8 Series and UR Family relays
Recommended Products & services
DAR Modular Reclosing Relays - Legacy
Manufacturing for this product has been discontinued. For more information, contact us.
The relays type DAR 2000 are multiple reclose electronic relays, manufactured in modular version, designed to perform automatically the three-phase reclose of a power breaker, tripped by the action of a protection relay.
DAR Modular Reclosing Relays - Legacy
Manufacturing for this product has been discontinued. For more information, contact us.
The relays type DAR 2000 are multiple reclose electronic relays, manufactured in modular version, designed to perform automatically the three-phase reclose of a power breaker, tripped by the action of a protection relay.
Recommended Products & services
D90Plus – Legacy
Manufacturing for this product has been discontinued. As an alternative, please refer to the D60 with Firmware 7.7 or newer and User Interface Option E: 7” Graphical Front Panel Display.
D90Plus – Legacy
Manufacturing for this product has been discontinued. As an alternative, please refer to the D60 with Firmware 7.7 or newer and User Interface Option E: 7” Graphical Front Panel Display.
Key Features
- Secure time-domain algorithm providing sub-cycle distance protection
- Phase distance with independent compensation settings for in-zone power transformers
- Ground distance with independent self and mutual zero-sequence compensation
- Out-of-step tripping and power swing blocking
- Directional overcurrent: phase, neutral and negative sequence
- Wattmetric zero-sequence directional power
- Under/over frequency
- Synchronism check for dual-breaker applications
- Single/three-pole four-shot dual-breaker autorecloser
- Customization of protection and control functions with independent protection FlexLogic™, FlexCurves™, and FlexElements™
- Advanced automation controller with independent automation programmable logic
- Bay control through front panel HMI
Protection & Control
Modern power systems are under increasing constraints in their ability to transmit power from generation facilities to major load centers, and are forced to operate closer to their natural stability limits. Under these conditions, the critical clearing angle – and corresponding critical clearing time – become progressively smaller and there is an increasing need to minimize the fault clearing time on these constrained circuits.
The D90Plus is ideally suited for application on circuits where fast fault detection and small breaker failure margin are required. The D90Plus allows transmission limits to be maintained or even increased while respecting the transient stability limits of the power system.
Key Features
- Continuous monitoring of AC input channels
- Metering - current, voltage, frequency, power, energy and synchrophasors as per IEEE C37.118
- Transient recorder - 128 samples/cycle, 1 minute or more of storage capacity
- Disturbance recorder – 1 sample/cycle, 5 minutes or more of storage capacity
- Event recorder - 8000 time tagged events, with 0.5 ms scan of digital inputs
- Comprehensive display of metering, phasors, maintenance and fault information via the front panel
Monitoring & Diagnostics
The D90Plus includes detailed metering and recording for all AC signals. Voltage, current, and power metering are built into the relay as a standard feature. Current and voltage parameters are available as total RMS magnitude, and as fundamental frequency magnitude and angle.
Digital fault recorder summary with the latest information on the events, faults, transients and disturbances.
Control screen for the pre-configured bay with breaker & disconnect control in multiple pages using dedicated pushbuttons on the front panel.
Advanced Automation
The D90Plus incorporates advanced automation features including powerful FlexLogic™ (user programmable logic) independent for protection and automation schemes. Combined with the communication capabilities, the D90Plus provides an advanced, highly flexible platform for substation automation applications. The D90Plus integrates seamlessly with other relays for distributed applications like interlocking and special protection schemes.
D90Plus user programmable protection logic and independent automation logic allows users to build custom protection and automation schemes.
Key Features
- Multiple protocols - IEC 61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC 60870-5-104
- Up to three independent IP addresses
- Increase network availability by reducing failover time to zero through IEC62439-3 "PRP" support
- Front USB port for high-speed communications
Advanced Communications
The D90Plus provides for secure remote data and engineering access, making it easy and flexible to use and integrate into new and existing infrastructures. Fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The availability of three independently configurable Ethernet options provide the means to create fault tolerant communication architectures in an easy, cost-effective manner. The D90Plus supports the most popular industry standard protocols enabling easy, direct integration into SCADA systems.
- IEC 61850
- DNP 3.0
- Ethernet Global Data (EGD)
- IEC 60870-5-104
- Modbus RTU, Modbus TCP/IP
- PRP as per IEC 62439-3
Front Panel
EnerVista™ Software
The EnerVista™ suite is an industry-leading set of software programs that simplifies every aspect of using the D90Plus relay. The EnerVista™ suite provides all the tools to monitor the status of the protected asset, maintain the relay, and integrate information measured by the D90Plus into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR setup software included with every UR relay, to carry out postmortem event analysis and ensure proper protection system operation. Learn More
Security - Enabling NERC CIP Comliance
Access Control
Multilin devices and relays are designed with simple but powerful security to enable reliability and compliance for virtually any project or implementation. With support for multi-level permissions and multi-factor supervisory controls, Multilin devices can help you manage the integrity of your system during commissioning, testing, implementation, and beyond. The UR and URPlus families provide separate authentication for settings and commands to the system. In addition, as discrete authentications for local and remote access, they also provide a supervisory control factor that can lock or unlock a device for configuration changes and other modifications.
Intrusion Detection
Multilin’s family of protection and control products can also help enable your security perimeter and intrusion detection programs. By providing essential alarming and logging of critical events, Multilin devices can help you detect potential breaches within your system and allow you to respond quickly and effectively. Specifically, unsuccessful access attempts are logged, alarmed, and lead to potential attackers being locked out. This ensures the reliability of your system during questionable activity, and a control factor that can lock or unlock a device for configuration changes and other modifications.
Auditing and Reporting
With the security audit trail reporting feature and support for event logging of key
activities such as configuration changes, Multilin devices can help ensure device and
protection system integrity, and perform forensic auditing of activities and changes
for compliance.
Enhanced Sub-Cycle Distance Protection
- Sub-cycle quadrilateral characteristic added for applications where this characteristic is preferred over the mho characteristic
- True digital CCVT filter to remove voltage transients introduced and provide accurate voltage information for distance protection – requires only three relay settings
Software Ease-of-Use:
EnerVista Viewpoint Engineer now available for graphical configuration of Protection and Automation FlexLogic™
Security Enhancements - Enabling NERC CIP compliance:
- Dual permission access requiring live permission from both the user and from SCADA operators before settings can be changed or commands can be given to the relay
- Remote and local setting and control passwords
- Configurable lockout responses to unsuccessful password access attempts
- Successful password access logged in events record
- Logging of user commands in the security audit trail report creates a record and sequence of events log for troubleshooting and security auditing
New and Enhanced Communications Capabilities
PRP as per IEC62439-3
High-Density I/O Options:
- New high density I/O option modules featuring either 23 optically isolated inputs or 12 Form-A outputs
- Ideal for applications like bay control and monitoring, where a large number of additional I/O are required