The GDC is a current detecting relay with detection being made by means of voltage applied to a high impedance unit. These relays are provided with measuring elements and are used mainly for the detection of restricted ground faults in transformers and rotating synchronous and asynchronous machines.

Applications

  • Transformer circulating current protection circuits

GDC Current Detecting Relay (Discontinued)

The GDC is a current detecting relay with detection being made by means of voltage applied to a high impedance unit. These relays are provided with measuring elements and are used mainly for the detection of restricted ground faults in transformers and rotating synchronous and asynchronous machines.

Applications

  • Transformer circulating current protection circuits

GCX51 is the type designation for a family of single phase, three-zone phase packaged relays. The first - and second-zone distance measurements are made by a unit having a reactance of ohm type characteristic and the third zone has a directional mho characteristic. 

GCY51 is the type designation for a family of single phase two-zone and three-zone mho phase distance relays for transmission line protection.

GCY Phase Packaged Directional-distance relay

GCX51 is the type designation for a family of single phase, three-zone phase packaged relays. The first - and second-zone distance measurements are made by a unit having a reactance of ohm type characteristic and the third zone has a directional mho characteristic. 

GCY51 is the type designation for a family of single phase two-zone and three-zone mho phase distance relays for transmission line protection.

Manufacturing for this product has been discontinued. As an alternative, please refer to the 3 Series relays.

GCX Phase Packaged Directional-distance Relay - Legacy

Manufacturing for this product has been discontinued. As an alternative, please refer to the 3 Series relays.

GE Vernova offers an industry-leading suite of multifunction servers, gateways, RTUs, and data concentrators for automating substation equipment and providing visibility to critical electrical assets found across the transmission and distribution power grids.

Gateways and RTUs

GE Vernova offers an industry-leading suite of multifunction servers, gateways, RTUs, and data concentrators for automating substation equipment and providing visibility to critical electrical assets found across the transmission and distribution power grids.

Multilin G100
Multilin G100

The G100 substation gateway offers a high-capacity, secure, modular, and substation-hardened set of hardware and software components designed to simplify the deployment, operation, and maintenance of automation systems – all in a compact form-factor for space constrained panels or cubicles.

More Info Multilin G100 Buy Now Multilin G100
Multilin G500
Multilin G500

The G500 substation gateway provides reliable and accurate collection of data from serial or LAN-based intelligent substation devices. It offers data logging, protocol conversion and runs automation applications, while consolidating functions such as HMI, Ethernet communications, time synchronization and cyber security features.

More Info Multilin G500 Buy Now Multilin G500

Multilin D20E
Multilin D20E 

The D20E is the next-generation input/output module for substation automation and SCADA RTU applications. It converts analogue and binary inputs to Ethernet signals using DNP3 or IEC 61850. It works perfectly with D20MX and G500.

More Info Multilin D20E Buy Now Multilin D20E
Multilin D.20 I/O Modules
Multilin D.20 I/O Modules 

D.20 I/O Modules are input/output modules for substation automation and SCADA RTU applications.

More Info Multilin D.20 I/O Modules Buy Now Multilin D.20 I/O Modules

Not finding the Gateway or RTU that you’re looking for? View legacy gateway & RTU products.

Manufacturing for this product has been discontinued, please refer to the 889 relay.

G650 - Legacy

Generator Protection and Control System

Manufacturing for this product has been discontinued, please refer to the 889 relay.

Communications icon
New and Enhanced Communication Capabilities
  • New process bus module supports IEC 61869 sample values, PTP master capabilities and SV switching (FW 7.9x)
  • New UR process bus modules supporting IEC61850-9-2LE Merging Units (FW 7.8x) Module Training available here
  • Support switchable IEC 61850 Ed. 1 and Ed. 2 and redundant SNTP (FW 7.7x)
  • New UR front panel with integrated 7” color, graphical display - providing operators with enhanced situational awareness (FW 7.6x)
  • High density I/O module supporting up to 120 inputs or up to 72 contact outputs – eliminating the need for additional discrete devices (FW 7.6x)
Communications icon
Cyber Security - CyberSentry UR (FW v7.xx)

CyberSentryTM enables UR devices to deliver full cyber security features that help customers to comply with cyber security requirements (NERC CIP, IEEE 1686, IEC 62443, etc):

  • Secured firmware upgrade: FW file includes hash code that enables authentication prior to being used for upgrading UR Relay (FW 7.9x)
Communications icon
Fully Compatible with IEC 61850-9-2LE or IEC61869 process bus schemes:
  • Can connect to up to 8 merging units over -9-2LE or 61869
  • Supports PRP, HSR, dual HSR and point-to-point process bus topology
  • Provides support for GE Vernova’s IEC 61850 HardFiber Process Bus Solution
Communications icon
Extended Oscillography Records (FW v7.xx)
  • Increased number of digital and analog channels (FW 7.90)
  • Supports IEEE C37.111-1999/2013, IEC 60255-24 Ed 2.0 COMTRADE 2013 standard (FW v7.40)
  • Configurable events allow for records of up to 45s at 64 samples per cycle
Communications icon
New and Enhanced Protection and Control Functionality
  • New Inrush detection element (FW 8.0)
  • Expanded Bay Controller Capabilities – providing a one box solution (FW 7.6x)

Key Features

  • Overall unit differential including transformer
  • Restricted ground fault, thermal overload protection, directional, time, instantaneous, phase, neutral, negative sequence and ground overcurrent protection
  • Split-phase protection
  • Loss of excitation, overexcitation plus dedicated harmonic/inrush detection
  • Third harmonic neutral undervoltage
  • Generator unbalance
  • Reverse and low forward power
  • Accidental energization
  • Synchronism check
  • Phase sequence reversal for pumped storage

Protection & Control

The G30 generator protection system provides comprehensive protection for small to medium-sized steam, hydraulic and combustion-turbine generators as well as applications that have both the generator and transformer in the same zone of protection. The G30 is ideal for protecting single and multi-pole generators with single or split-phase winding configurations of generators. The G30 includes advanced automation and communication capabilities, extensive I/O options, and powerful fault recording features that can simplify fault and disturbance troubleshooting and minimize generator downtime. As part of the UR family, the G30 provides superior protection and control.

Functional Block Diagram
G30 Block Diagram
ANSI® Device Numbers & Functions

 

Device NumberFunction
24Volts Per Hertz
25Synchrocheck
27PPhase Undervoltage
27TNThird Harmonic Neutral Undervoltage
27XAuxiliary Undervoltage
32Sensitive Directional Power
40Loss of Field Relay
46Generator Unbalance
49Thermal Overload
50GGround Instantaneous Overcurrent
    
Device NumberFunction
50NNeutral Instantaneous Overcurrent
50PPhase Instantaneous Overcurrent
50SPSplit Phase Instantaneous Overcurrent
50/27Accidental Energization
51GGround Time Overcurrent
51NNeutral Time Overcurrent
51PVPhase Time Overcurrent with Voltage Restraint
59NPhase Overvoltage
59XAuxiliary Overvoltage
    
Device NumberFunction
59_2Negative Sequence Overvoltage
67_2Negative Sequence Directional Overcurrent
67NNeutral Directional Overcurrent
67PPhase Directional Overcurrent
81OOverfrequency
81RRate of Change of Frequency
81UUnderfrequency
81RGFRestricted ground fault
87GTGenerator/Transformer Differential
 Harmonic/Inrush detection

Key Features

  • Metering - current, voltage, power, energy, frequency
  • Oscillography – analog and digital parameters at 64 samples/cycle
  • Event Recorder - 1024 time tagged events with 0.5ms scan of digital inputs
  • Data Logger - 16 channels with sampling rate up to 1 sample / cycle
  • Setting for security audit trails for tracking changes to G30 configurations
Monitoring & Diagnostics
Monitoring & Diagnostics The G30 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into HMI or SCADA monitoring and control systems like Viewpoint Monitoring as shown.
Advanced Automation

The G30 incorporates advanced automation features including powerful FlexLogic™ programmable logic, communication, and SCADA capabilities that far surpass what is found in the average generator relay. The G30 integrates seamlessly with other UR relays for complete system protection, including unit and auxiliary transformers, and balance of plant protection.

FlexLogic™ diagram FlexLogic allows for the customization of the G30 to operate and control the breakers and other auxiliary devices needed to fit most generator protection schemes and applications.

Key Features

Complete IEC 61850 Process Bus solution providing resource optimization and minimizing total P & C life cycle costs

  • Three independent 100Mbps Ethernet ports enable purpose specific LAN support that eliminates latency effect of heavy traffic protocols on mission critical communication services
  • Embedded IEEE 1588 time-synch protocol support eliminates dedicated IRIG-B wiring requirements for IEDs
  • Direct I/O secures high-speed exchange of binary data between URs
  • Increase network availability by reducing failover time to zero through IEC62439-3 PRP, HSR or dual HSR support

Advanced Communications

The G30 provides advanced communications technologies for remote data and engineering access, making it the easiest and most flexible generator protection relay to use and integrate into new and existing infrastructures. Direct support for fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The available three independent and redundant Ethernet options provide the means to create fault tolerant communication architectures in an easy, cost-effective manner.

The G30 supports the most popular industry standard protocols enabling easy, direct integration into DCS and SCADA systems.

  • IEC 61850-9-2LE or IEC 61869 point-to-point or networked or IEC61850-9-2 Hardfiber process bus support
  • DNP 3.0 (serial & TCP/IP)
  • Ethernet Global Data (EGD)
  • IEC 60870-5-103 and IEC 60870-5-104
  • Modbus RTU, Modbus TCP/IP
  • HTTP, TFTP, SFTP and MMS file transfer
  • Redundant SNTP and IEEE 1588 for time synchronization
  • PRP as per IEC 62439-3
  • Supports Routable GOOSE (R-GOOSE)

Interoperability with Enbedded IEC 61850

Use the G30 with integrated IEC 61850 to lower costs associated with generator protection, control and automation. GE Vernova’s leadership in 
IEC 61850 comes from thousands of installed devices and follows on years of development experience with UCA 2.0.

HardFiber system

The G30’s IEC 61850 Process Bus module is designed to interface with the Multilin HardFiber System, allowing bi-directional IEC 61850 fiber optic communications. The HardFiber System is designed to integrate seamlessly with existing Universal Relay applications, including protection functions, FlexLogic, metering and communications. Learn more

The G30 can also connect to GE Vernova MU320 or third-party merging units using standard IEC 61869 or IEC 61850-9-2LE communication protocols.

Cyber Security - CyberSentry™ UR (FW v7.4xx)

CyberSentry enables UR devices to deliver full cyber security features that help customers to comply with NERC CIP and NITIR 7628 cyber security requirements through supporting the following core features:

Secure FW upgrade

UR FW files v7.9 and up now include a hash code that allows for authentication prior to being used for upgrading UR devices.

Password Complexity

Supporting up to 20 alpha- numeric or special characters, UR passwords exceed NERC CIP requirements for password complexity. Individual passwords per role are available.

AAA Server Support (Radius)

Enables integration with centrally managed authentication and accounting of all user activities and uses modern industry best practices and standards that meet and exceed NERC CIP requirements for authentication and password management.

Role Based Access Control (RBAC)

Efficiently administrate users and roles within UR devices. The new and advanced access functions allow users to configure up to five roles for up to eight configurable users with independent passwords. The standard “Remote Authentication Dial In User Service” (Radius) is used for authentication. 

Event Recorder (Syslog for SEM)

Capture all cyber security related events within a SOE element (login, logout, invalid password attempts, remote/local access, user in session, settings change, FW update, etc), and then serve and classify data by security level using standard Syslog data format. This enables UR devices integration with established SEM (Security Event Management) systems.

EnerVista™ Software

The EnerVista™ suite is an industry-leading set of software programs that simplifies every aspect of using the G30 relay. The EnerVista™ suite provides all the tools to monitor the status of the protected asset, maintain the relay, and integrate information measured by the G30 into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR setup software included with every UR relay, to carry out postmortem event analysis and ensure proper protection system operation. Learn More

Enervista Software
Applications
  • When an IED is not equipped for optical communication

FSD Fiber Subsystem Datalink (Discontinued)

Applications
  • When an IED is not equipped for optical communication

The FSC equipment is a synchronous digital multiplex equipment with integrated drop and insert multiplexer module and application/interface modules designed for the electrical utility industry. The system provides an optical interface operating at a 51.84 Mb/s rate with up to 672 DS-0 channels, or a 155.52 Mb/s rate with up to 2016 DS-0 channels.

Applications 
  • Full SONET/SDH based multiplexer

FSC Fiber Optic System Communications (Discontinued)

The FSC equipment is a synchronous digital multiplex equipment with integrated drop and insert multiplexer module and application/interface modules designed for the electrical utility industry. The system provides an optical interface operating at a 51.84 Mb/s rate with up to 672 DS-0 channels, or a 155.52 Mb/s rate with up to 2016 DS-0 channels.

Applications 
  • Full SONET/SDH based multiplexer

Sales of the ILMS offering has been discontinued

Multilin Intelligent Line Monitoring System - Legacy

Delivering actionable intelligence for improved reliability and efficiency

Sales of the ILMS offering has been discontinued

Overview

The Multilin Intelligent Line Monitoring System is an end-to-end line monitoring solution with advanced analytics that provides actionable intelligence to distribution utilities to improve the reliability and efficiency of their networks.

Analytical Applications
Analytical Applications
  • Feeder visualization
  • Fault detection, location and analysis and maintenance prioritization (Multilin X-NET)
  • Dynamic line rating calculation and analysis (Multilin T-NET)
SNG
Sensor Network Gateway (SNG)
  • Acts as a communications gateway for distribution network and weather information critical for supporting advanced applications
  • Equipped with a GPS transceiver that synchronizes the entire system, enabling GE Vernova’s advanced analytics
  • Provides multiple options for communications backhaul to analytical applications providing installation flexibility
Line sensors
Line Sensors
  • Provides periodic time synchronized measurements to facilitate improved situational awareness and operations:
    • Electrical current, both amplitude and phase
    • Conductor surface temperature
  • Detects fault conditions facilitating rapid identification and notification
  Key Benefits
  • Extended visibility into the distribution network
  • Reduced cost of ownership with GE Vernova’s sensors designed for easy installation on live networks
  • Designed to meet the challenges of capturing faults in both low and high impedance grounding treatments
  • Advanced analytical applications enabled by GE Vernova’s patented time synchronized data
  • Remote firmware upgrade enabling further application development and compliance with regulatory and operational requirements
  • Time synchronized measured data in DNP3 format

Fault Detection, Location and Analysis Application (X-NET Software)

 Fault notification to smart phones
Feeder segmented history

The advanced analytics delivered by the X-NET application are designed to meet the challenges of capturing faults in both low and high impedance grounding treatments. The Intelligent Line Monitoring System delivers the necessary field visibility and advanced analytics to capture and report the location of ground and phase to phase faults as well as cross country faults in high impedance grounding schemes.

Fault Detection, Location & Analysis
  • Monitors the distribution network 24/7 for events and faults
  • Automatically filters events from faults based on utility defined configuration to avoid nuisance reports
  • Identifies fault location alerting operators visually and notifying repair crews via email and SMS messaging
  • Provides a cycle by cycle plot of fault activity
Maintenance Prioritization 

The X-NET Software enables the utility to effectively prioritize maintenance expenditure by:

  • Maintaining a database of events to facilitate identification of repetitive incidences, comparison of feeder performance and definition of preventive maintenance programs
  • Graphically depicting outage history for each feeder section

The X-NET Application enables utilities to:
 

  • Target where to spend maintenance funds based on performance instead of age of assets
  • Direct field crews to feeder sections where maintenance is needed
  • Guide maintenance work required by the nature and frequency of feeder faults indicated by frequent re-closer activity
  • Categorize maintenance required based upon repetitive transients indicative of:
    • The need for tree trimming
    • Salt build-up
    • Equipment degradation

Dynamic Line Rating Application (T-NET Software)

Current loading and available capacity
Current loading and available capacity

GE Vernova's Multilin T-NET advanced analytics compute dynamic line ratings based on prevailing conditions enabling distribution utilities to better manage their feeders, avoid conductor degradation, and knowledgeably deploy sustainable generation. The Intelligent Line Monitoring System employs weather data including a weather station and/or an ultrasonic anemometer input and uses wind speed and direction averaging techniques to deliver enhanced dynamic line rating analytics enabling utilities to set increased circuit ratings based on a greater understanding of prevailing conditions.

In addition to delivering measured data in DNP3 format, GE Vernova's dynamic line rating application provides actionable information enabling utilities to:

  • Understand the current loading on the feeder
  • Recognize feeders nearing their rated capacity
  • Identify additional available line capacity based on prevailing conditions
  • Detect site specific icing conditions to enhance storm operation decisions and response
  • Calculate line sag based on prevailing conditions

Feeder Visualization Application

3-Phase current

In addition to delivering measured data in DNP3 format, GE Vernova's feeder visualization application increases situational awareness along distribution feeders and enables utilities to operate and respond based on prevailing conditions, not static or seasonal estimates. This application provides actionable information enabling utilities to:

  • Analyze 3 phase current along the feeder
  • Balance phases to extend circuit capabilities and delay capital expenditures
  • Identify conductor loading issues due to phase imbalance and take corrective action
  • Identify line regulator loading issues and take corrective action

GE Vernova's Intelligent Line Monitoring system is time synchronized enabling data from multiple locations along the distribution network to be aligned to within 40µS. Accurate time synchronization enables the delivery of positive, negative and zero sequence currents at each measuring location along with substation voltage.

Time Synchronized Communications with the Sensor Network Gateway

Sensor network gateway

As part of the Intelligent Line Monitoring System, the Sensor Network Gateway (SNG) plays a vital role in ensuring connectivity between the applications and the field, providing visibility along the distribution network. The SNG provides a communications gateway for distribution network and weather information that is critical for advanced applications such as fault location and analysis, dynamic line rating, maintenance planning and feeder visualization. Alternatively the SNG delivers measured data in DNP3 format to head end systems.

The SNG provides two way communications to the line sensors by 2.4 GHz radio. The SNG receives weather data from to the weather station and/or ultrasonic anemometer by a hardwired link. The SNG also records voltage, both amplitude and phase, at 32 samples per cycle via substation or feeder voltage transformers (VT’s). The SNG is equipped with several backhaul options for communicating with the advanced applications including 2G/3G GRPS/UMTS as well as serial and Ethernet communication ports. Each SNG is equipped with a GPS transceiver that synchronizes the entire system, enabling GE Vernova’s advanced analytics.

The SNG is versatile and can be installed along the distribution feeder communicating with the line sensors or in a substation for voltage monitoring. Typical feeder installation scenarios include a single SNG with three sensors (one sensor per phase) or a single SNG with six sensors located at a branch port or feeder tap enabling it to effectively monitor two circuits at one site. Radio range between the line sensors and the SNG is typically 30 meters/100 feet, and the SNG is normally mounted on the same pole or structure underneath the sensors. The SNG is a low power device and can be powered by a solar panel or by a 100V/250V AC power supply.

Advanced Overhead Line Sensing

Line sensor

As part of the Intelligent Line Monitoring System, the sensors play a key role in providing visibility along the distribution network. The sensor measures and records the current, both amplitude and phase, at 32 samples per cycle, and communicates to the SNG via an on-board 2.4 GHz radio.

The sensor is configured to detect fault conditions facilitating rapid identification and notification. In addition, the sensors can be configured to provide periodic measurements to facilitate improved situational awareness and operations. The sensor can be supplied with an optional temperature probe on a flying lead that measures the surface temperature of the conductor facilitating dynamic line rating analysis and conductor temperature monitoring.

Installation of the Multilin FMC-T6 line sensor can be completed in just minutes on a live line using either hot-stick or hot-glove. Sensors can be installed on 480V to 140kV feeders and will sit on conductors ranging from 10 mm to 28 mm in diameter. The sensor commences operation as soon as it is closed around the conductor and a small flashing LED mounted in the sensor housing indicates that it is operational. The magnetic field of the line provides the power for the sensor and also charges a 48 hour battery back-up that keeps the sensor operational in the event of an outage.

Application Data Specifications

Application Data Specifications

System Management Specifications

System Management Specifications

Software Specifications

Software Specifications

Certifications

Certifications

Type Tests

Type Tests

Manufacturing for this product has been discontinued. As an alternative, please refer to the Multilin 350 and P14N Relays.

FM2 Feeder Manager 2 - Legacy